A brick bungalow off Van Dyke in 48089, one pipe steam, original cast iron boiler, and the complaint is noise: gurgling at the boiler and a bang in the living room radiator every morning. Quick observation first. The water in the sight glass is brown and jumping up and down a couple of inches. You can see the line where it ran on the glass.
That bouncing water line tells us the boiler water is dirty. Oil, rust and sediment foam on the surface, the boiler surges, and wet steam carries water up into the mains. That water slams around in the pipes. We drain and flush the sediment, then skim the surface through the skim tapping until the water comes out clear and the line settles.
Then we check the pitch. South Warren homes have settled for 60 to 80 years, and a main or runout that has sagged holds water where steam needs to move. We level it with a string or a level and re-hang it so condensate can run back to the boiler. We also check that the radiator valves are fully open, not halfway.
Most of the time a South Warren one pipe system is sound as built. It needs clean water, correct pitch and low pressure, not a new boiler. We finish with a low water cutoff test the homeowner can watch, set the pressuretrol around half a pound, and leave a short note on the boiler with what we did.