Here is a common 48092 call: a split-level off 12 Mile, the boiler fires for a few minutes, shuts off, and comes back on. The lower level is warm, the upper bedrooms are cool. Quick observation first. The gauge needle barely moves, yet the burner keeps cutting out. That gap between the gauge and the burner is the clue.
We take the pressuretrol off and look at the pigtail under it. On a lot of Van Dyke corridor homes, it is packed with sludge. The pressuretrol is reading a pocket of trapped pressure, not the boiler. So it shuts the burner too soon, or never shuts it at all. Either way, the house heats in short bursts and the upper split stays cold.
We clean or replace the pigtail and reset the pressuretrol, cutting in around half a pound and out under 2. Then we look at the main vents, because a split-level has radiators at three levels and the mains need to vent fast enough to reach them. Undersized main vents keep the top level waiting for steam long after the burner shuts off.
Before we leave, we watch a full cycle with the homeowner: steam to the far radiators, the burner shutting off on the thermostat, not the pressuretrol. We also show them how to read the gauge and the sight glass. If it starts short cycling again, they know what to look at and what to tell us on the phone.